Page 1 of 6 02/08/00
Maine Public Service
Company
Settlement and Load
Profiling Methodology
Chapter 321 Report #2
The following report will describe in outline the methodology and the software
that Maine Public Service Company (MPS) plans to use for settlement and load profiling
under Retail Access. Central to this methodology is the method used to calculate multiple
independent competitive energy supplier loads, on a daily/hourly basis, which are
dispersed across a single transmission and distribution system. The Northern Maine
Independent System Administrator (NMISA) will use this information to settle, i.e.
balance or match, each independent competitive supplier’s energy supply against their
assigned load responsibility and to allocate supplier load responsibility for shared
resources. Chapter_321 of the Maine Public Utilities Commission (MPUC) Rules
establishes the daily and monthly reporting requirements for reporting hourly and
monthly load obligations of competitive electricity providers operating in Maine to the
NMISA as well as to ISO-NE. Chapter_321 of the MPUC Rules also governs
telemetering, load profiling, information access, and data transfer. Section 9 requires the
Maine utilities to file two methodology reports: a report on sampling and data validation,
and a report on profiling and load estimation methodology. The first MPS report on load
research methodology was filed on December 1, 1998. This report is the second in the
series. Since the other two investor owned utilities in Maine, Bangor Hydro Electric
Company (BHE) and Central Maine Power Company (CMP) have essentially the same
requirements, the many of the elements of this report borrow heavily from software
vendor documentation and the CMP methodology report published previously.
Load Profiling
The method of identifying a customer’s distinctive hourly load curve over a
twenty-four hour period is referred to as “load profiling.” MPS uses three approaches to
collecting load data for customer classes. Most smaller customers do not have meters
that are capable of sending hourly usage data back to the utilities, it is necessary to use a
representative sample to establish the typical load shape of the customer. For these
customers, since only the total monthly individual customer energy usage is known, it is
necessary to estimate the hourly usage of the individual customer. These customers are
sometimes referred to as “profiled customers.” Most individual large customers, on the
other hand, have meters that record actual hourly customer usage and send this data back
to the utilities by telephone. For these customers, hourly usage is normally known
exactly. These customers are often referred to as “telemetered customers.” On occasion
telemetered customer loads need to be estimated when actual hourly meter data is not
available. In this case the profile will be based on available usage history for the
customer, usually a “static profile” as described below. Certain other customer loads are
not metered at all, lighting customers for example, and are based on estimates of hours of
use because they are entirely predictable These are referred to as “deemed profiles.”
The method of load profiling can affect the hourly load estimate associated with the
customer, and as a result affect the resulting financial
settlements between independent
Page 2 of 6 02/08/00
competitive suppliers at the NMISA. There are six general profiling methods in use to
estimate hourly loads that are not known precisely:
Dynamic metering is done by installing telemetering on a sample of customers
from each profile group. The meters are interrogated daily, providing a profile for the
day that represents actual load.
Dynamic modeling is a relationship between load and weather. Typically this would
be a regression of the historical load of customers in a sample against the weather that
occurred during the time of the load. The regression could be either a daily
regression or an hourly regression for any season and day type combination.
Proxy day profiling is accomplished by selecting a day in history that most closely
matches the day being estimated. The proxy day can be chosen based on either
system load or weather. Actual data from the sample for the selected proxy day is
then used to create the profile.
Static profiles are typical day representations for any season and day type
combination. Static profiles do not reflect operating conditions of the day being
estimated.
Calendar rotation is simply rotating a calendar of historical interval data to reflect
the calendar of the time being estimated. Calendar rotation also does not reflect
operating conditions of the day being estimated.
Deemed profile (see above)
Each of these methods of estimating class or segment hourly energy usage varies
in terms of accuracy and the degree of predictability for an individual energy supplier. A
higher level of accuracy implies that there is less “unaccounted-for energy” (UFE)
between the sum of all estimates and the actual system energy load. A higher level of
accuracy is more costly to implement because more elaborate equipment is required as
well as more detailed calculations to handle more variables. Dynamic metering is most
accurate but also most costly. As you move down the list above, cost decreases but the
amount of UFE remaining after the estimate is larger. The optimum method for profiling
should strike a balance between cost, accuracy, and predictability.
Concerns of Standard Offer Bidders
Competitive electricity providers, interested in bidding on the Standard Offer,
expressed a concern that if the method used to derive load profiles was not decided upon
until after bids were submitted, then they might be at a competitive disadvantage if their
bid was based on a method different from the method they used as the basis for their bid.
An additional concern expressed was that each utility might choose a different
methodology and thereby increase the complexity to a supplier operating in multiple
service territories.
Page 3 of 6 02/08/00
In response to the concerns of standard offer bidders, the three Maine investor
utilities MPS, BHE and CMP in conjunction with the MPUC agreed to use “Typical
Day” (static profile) methodology in the beginning to simplify the methodology. It was
agreed that these profiles would consist of different week-day and weekend-day profiles
for each of twelve months for each profiled segment, i.e. residential, commercial, small
industrial. Holidays will be modeled using the weekendday profile.
Software Used
MPS has purchased a license to use Load Vision developed by ICF Consulting,
Inc. Load Vision is a profiling, scheduling, and settlement tool that is currently used by
many utilities and energy suppliers across the U.S. to forecast and settle loads in energy
markets opened up to retail competition. Load Vision provides many capabilities,
perhaps the most important of which is auditability. Information flowing into Load
Vision database is "time-stamped" so that prior settlement runs can be recalculated at any
time. Currently the Load Vision is being used by the three investor owned utilities in
Maine, Bangor Hydro Electric Company, Central Maine Power Company, and Maine
Public Service Company.
How Load Vision Calculates a Static Profile
Traditionally static profiles are calculated by averaging hourly values for each
season and day type combination. This results in a flattened load shape, i.e. the average
load shape peak is generally too low and the average load shape trough is generally too
high. Load Vision improves this calculation by using a rank average method, as
described in Appendix A in the Load Vision documentation. This method results in a
static profile that more accurately reflects the typical day usage pattern, including the
height of the peaks and depth of the troughs.
How Load Vision Estimates the Daily Load
The daily load estimation process will consist of loading various types of data into
Load Vision, customer add/drop data, customer cycle energy use data, telemetered
customer data, and daily weather data as appropriate. Customer class segment profile
data will be updated on a monthly basis as the data becomes available. Data loading will
be a semi-automated process for the forseeable future.
1. Profiled Customer Load Estimation with Load Vision uses the following
four process steps:
Determination of the hourly profiled load for each
customer profile
class- As described above, a static profile will be used for each of the
three profile classes defined in Chapter 321, and a deemed profile will be
used for unmetered load.
Scale the profiled load for each hour by the relevant
Loss Factor -
The loss factor is assigned to the customer depending on the season and
voltage level.
Page 4 of 6 02/08/00
Determination of each customer's Usage Factor - The Energy Usage
Factor (EUF) characterizes how the customer's usage relates to the
average energy usage for a particular profile class. The EUF is defined as
the ratio of the metered usage to the aggregate hourly profiled loads for
the customer's profile class for a billing period. If a new customer has no
historic or billed usage, an hourly Usage Factor of 1.0 will be assigned to
that customer.
Derive the usage-adjusted profile load for each customer. The
customer usage-adjusted profile is the loss-adjusted profile multiplied by
the customer Usage Factor.
2. Telemetered Customer Load Determination - For telemetered customers, if
interval meter data is available for the day, the hourly load is the metered
usage multiplied by the customer's Loss Factor. The Loss Factor assigned to
the customer depends on the season and voltage level. If a telemetered
customer's interval data is not available for the day and needs to be estimated,
the missing data will be estimated using the customer's historical usage. The
hourly loads using the day profile will be calculated using the method for
profiled load detailed above.
3. Settlement or Summation of Supplier Hourly Loads - During this step
customer class hourly loads created in the previous procedures are aggregated
into total loads for each supplier.
4. Reconciliation of Supplier Hourly Loads to System
Load:
Determination of the Hourly Load Difference using the hourly system
load as the baseline.
Determination of the Supplier profile load by allocating the hourly load
difference to profiled customers only requires that all telemetered loads for
a supplier be subtracted from that supplier's total hourly load. The resulting
value is the supplier's hourly profile load.
Calculate the Load Allocation Ratio- The hourly load difference is
allocated to a supplier based on the ratio of that supplier's profiled load to
the aggregate profile load of all suppliers.
Allocation of the Hourly Load Difference to the
Supplier's nontelemetered
customers - This reconciliation step distributes the hourly
load difference back to the non-telemetered customers using the load
allocation ratio. The allocated amount is the product of the hourly load
difference and the load allocation ratio. This allocation amount is added to
the supplier's hourly profiled load to derive the
reconciled profile load.
Page 5 of 6 02/08/00
Calculate the Supplier Hourly Load Obligation - The supplier’s hourly
load obligation is the sum of the supplier's hourly telemetered load and the
reconciled profiled load.
MONTH-END ADJUSTMENTS
After all meter readings for each month have been obtained, MPS will re-estimate
the hourly load for the month. The process will be identical to the daily process but the
month-end calculation will use available data collected subsequent to the original
calculation. The usage factors will be recalculated to reflect each customer's most recent
billing period’s usage. This usage will better reflect usage during the month being reestimated.
The calculations for the month-end adjustment are the same as described in
the daily process: total profiled load with losses is added to total telemetered load with
losses and compared to total system load. Any hourly differences are allocated back to
suppliers based on their proportion of the total profiled load.
The total month-end energy will also be adjusted to reflect Net Energy Billing customers.
Excess generation (or negative usage) cannot be reported in the daily load settlement
process but it is possible to adjust the month end numbers to reflect excess generation by
net energy billing customers. The adjustment would reduce the supplier's load obligation
by the amount of the excess generation and would proportionately increase the load
obligation of all other suppliers.
REPORTING REQUIREMENTS
Daily estimates of supplier load obligation will be reported to NMISA within 36
hours after the end of the day being reported. The load obligation will be reported by
Load Asset ID to the NMISA. will send suppliers their load obligation at the same time
it is sent to NMISA. Month end numbers will be reported to NMISA within 45 days after
the end of the month. Month-end numbers will be the revised total energy for the month,
reported by Load Asset ID. MPS will send suppliers their hourly loads that comprise
this new estimate within 2 days after reporting to NMISA.
SUMMARY
MPS will use a static profiling methodology for the three profile groups defined
in Chapter 321. The profiles will represent 12 months and 2 day types (week-day and
weekend-day). Holidays will be estimated using a weekend profile. Unmetered load will
be estimated using a deemed profile that is determined by the number of daylight hours.
Telemetered customers will be settled using their actual load. If the actual data is not
available for telemetered customers on a given day, a historical day profile for the
individual customer will be used.
Page A- 1 of 3 02/08/00
APPENDIX
STATIC PROFILING METHODOLOGY
The rank average method that Load Vision uses to create typical day or static profiles
improves on traditional static profiling methods by preserving the levels of the peaks and
valleys in the final load shape. The rank average approach involves various steps that are
detailed below.
Step 1: Group load research sample meter data based on
season and day-type
combination - The load data will be grouped into 12 month with 2 day types
for each profile group. Holidays will be put into the included with weekends.
Example:
12 Season (month) /2 Day-Type Calendar
Season 1 (January) Season 7 (July)
Season 2 (February) Season 8 (August)
Season 3 (March) Season 9 (September)
Season 4 (April) Season 10 (October)
Season 5 (May) Season 11 (November)
Season 6 (June) Season 12 (December)
Day Type 1 (Weekday): Mon, Tue, Wed, Thurs, Fri
Day Type 2 (Weekend): Sat, Sun, Holiday
Step 2: Create a weighted average of all observations
for the profile for each day.
Example:
Weights are assigned by the user within Load Vision:
Profile Load Research Meter Weight
Residential R123 1
Residential R456 1
Residential R789 1
(Note: weights will reflect weights assigned to each meter in the sampling process)
Illustrative Observations from the meter:
Load Research Meter Day Hour1 Hour2 Hour3 Hour4 …
R123 12/1/98 30 50 40 60 …
R456 12/1/98 35 55 45 65 …
R789 12/1/98 40 60 50 70 …
Page A- 2 of 3 02/08/00
Result:
Profile Day Hour1 Hour2 Hour3 Hour4 …
Residential 12/1/98 35 55 45 65 …
Residential 12/2/98 60 70 50 55 …
Residential 12/3/98 55 70 55 60 …
Residential 12/4/98 32 60 45 50 …
Step 3: Average the load values to create an Average
Load Shape
Example:
Season (month) 12, Day-Type 1
Profile Day Hour1 Hour2 Hour3 Hour4 …
Residential 12/1/98 35 55 45 65 …
Residential 12/2/98 60 70 50 55 …
Residential 12/3/98 55 70 55 60 …
Residential 12/4/98 32 60 45 50 …
Result:
Profile Day Type Hour1 Hour2 Hour3 Hour4 …
Residential Weekday 45.5 63.75 48.75 57.5 …
Step 4: Sort the load values in descending order to
create a Load Duration Curve
Example:
Season 12, Day Type 1
Profile Day Hour1 Hour2 Hour3 Hour4 …
Residential 12/1/98 65 55 45 35 …
Residential 12/2/98 70 60 55 50 …
Residential 12/3/98 70 60 55 55 …
Residential 12/4/98 60 50 45 32 …
Step 5: Average the Load Duration Curve values to
create an Average Load
Duration Curve
Example:
Result:
Profile Day Type Hour1 Hour2 Hour3 Hour4 …
Residential Weekday 66.25. 56.25 50 43 …
Page A- 3 of 3 02/08/00
Step 6: Map the Average Load Duration Curve to the
Average Load Shape
Example:
Average Load Shape:
Profile Day Type Hour1 Hour2 Hour3 Hour4 …
Residential Weekday 45.5 63.75 48.75 57.5 …
Average Load Duration Curve:
Profile Day Type Hour1 Hour2 Hour3 Hour4 …
Residential Weekday 66.25 56.25 50 43 …
Resulting Load Profile:
Profile Day Type Hour1 Hour2 Hour3 Hour4 …
Residential Weekday 43 66.25 50 56.25 …
This methodology preserves the same usage pattern as a traditional static profiling
approach (the average load shape shown above) but also preserves the level of peaks and
troughs obtained through the average load duration curve. The result is a static profile
that better represents a "typical day."